On the definition of their correct roughness

Interior side of element walls

An element wall should give a monolithic impression when in use. There is to be a firm bond between the shells and the filling concrete. The bond achieved has an influence mainly on:

the load-bearing action, that is, the force transmissible in the joint (DIN EN 1992-1-1 very smooth to interlocked);

the composite action in terms of soundproofing (is a thick wall vibrating, or are three slabs vibrating);

the composite action in terms of tightness in water-impermeable structures.

For the structural approach, DIN EN 1992-1-1 specifies four options ranging from very smooth, smooth, rough to very rough. These options are illustrated in the image taken from Lenz und Zilch [1].

Rough is thus achieved by means of grains protruding by 3 mm (exposure), or by producing a basic roughness with a mean peak-to-valley height about the theoretical mean surface line of ± 1.5 mm.

The new DAfStb (Deutscher Ausschuss für Stahlbeton e.V. = German Committee for Reinforced Concrete) guideline “Wasserundurchlässige Bauwerke aus Beton” (Water-Impermeable Structures Made of Concrete) scheduled for publication at the end of 2017/ beginning of 2018 now adopts the requirement of “rough” according to DIN EN 1992-1-1, meaning that the required mean peak-to-valley height is increased from 0.9 mm to 1.5 mm.

The changes also include a new requirement to check and document the peak-to-valley height at the plant and to perform random visual checks on the construction site.

However, the guideline on water-impermeable structures additionally specifies for a bond and a connection free of cavities to be produced between the core concrete and the shells. This goes beyond roughness. Some invitations to tender even now require the aggregate to be exposed and the entire cement paste to be removed. It certainly does not make sense to remove the entire cement paste, but removing it “only” on the protruding coarse aggregates, that is, creating an exposed aggregate concrete texture, is not technically feasible for element walls. The contribution explains the ramifications of the new provisions for both the manufacturers and the construction site based on case examples.

x

Related articles:

Issue 10/2020

Determining the roughness of precast concrete slabs correctly: first real-life tests analyzed

The German Guideline on Waterproof Concrete Structures provides the option of also using precast wall panels or floor slabs as waterproof structures. For this purpose, a cavity-free bond must be...

more
Issue 07/2019

Precast wall units conforming to the new Guideline on Waterproof Concrete Structures – Initial experience

Introduction The new Guideline on Waterproof Concrete Structures (December 2017 edition, [1]) has been available since February 2018. DBV Heft [Volume] 43 [3] contains a summary of the revised...

more
Issue 02/2016 Precast concrete elements

Correct execution and the choice of in-situ concrete ­determine successful performance

Precast concrete elements, double walls with in-situ concrete core, and precast floor plates are enjoying increasing popularity owing to the fact that their exterior surfaces are smooth-formed in the...

more
Issue 06/2016 Greencode

Multifunctional ­insulation wall

The innovative Greencode insulation wall unit makes it possible to benefit from an industrial production environment as early as at the shell construction stage. Each wall unit is designed...

more
Issue 02/2015 Sandwich elements of lightweight aggregate concrete (LAC) with open structure

Highly insulating three-layer external wall elements

The European Union has made it its goal to considerably lower CO2 emissions in the coming years. To achieve this goal, a number of directives, laws and regulations were passed, amended, and made...

more